Determination of the hydrogen diffusion coefficient in transformer oil
- 24 March 2011
- journal article
- Published by Pleiades Publishing Ltd in Technical Physics
- Vol. 56 (3) , 421-422
Abstract
The hydrogen diffusion coefficient in transformer oil is determined by optically monitoring the dynamics of the hydrogen bubble dissolution in pure degassed oil. The diffusion coefficient is found to be roughly two orders of magnitude smaller than those determined earlier. This result is of great importance for chromatographic analysis of gases dissolved in transformer oil, since it gives grounds to suspect that hydrogen is not so volatile as implicitly believed in a number of works. Accordingly, the reliability of diagnostic data for high-voltage oil-filled equipment improves.Keywords
This publication has 1 reference indexed in Scilit:
- The dissolution of a stationary spherical bubble beneath a flat plateChemical Engineering Science, 2006