Abstract
This paper presents a support vector regression-based postfault current zero estimation technique for single-line-to-ground faults on series-compensated transmission lines. The same can be used for controlled fault interruption, which, in turn, can help to control the arcing time of the circuit breakers (CBs). The proposed technique is applied on a 400-kV series-compensated transmission line with series compensation placed at the middle of the line. Various power system parameters like fault resistance, load angle, fault inception angle, source impedance, fault location, and compensation level are varied to generate a large number of simulation cases involving single-line-to-ground faults. Since the incorrect current zero detection may cause an adverse impact on various CB components, especially contacts and parts of the interrupting chamber, the postfault zero estimation for each test case is performed multiple times using successive postfault sample windows of the faulted phase. The estimation performed in this way bestows correct zero crossing detection for more than 95% of test cases which proves the effectiveness of the proposed algorithm. The blind dataset and cross-validation technique have also been applied for validating the performance of the proposed algorithm.Keywords
This publication has 10 references indexed in Scilit:
- Combined Wavelet-SVM Technique for Fault Zone Detection in a Series Compensated Transmission LineIEEE Transactions on Power Delivery, 2008
- A method for controlled fault interruption based on predicted current behavior2008
- The detection of abrupt changes using recursive identification for power system fault analysisElectric Power Systems Research, 2007
- Application of Abrupt Change Detection in Power Systems Disturbance Analysis and Relay Performance MonitoringIEEE Transactions on Power Delivery, 2006
- Abrupt change detection in power system fault analysis using adaptive whitening filter and wavelet transformElectric Power Systems Research, 2006
- An adaptive, self-checking algorithm for controlled fault interruption2005
- A new algorithm enabling controlled short circuit interruptionIEEE Transactions on Power Delivery, 2003
- Controlled closing on shunt reactor compensated transmission lines. I. Closing control device developmentIEEE Transactions on Power Delivery, 1997
- Controlled closing on shunt reactor compensated transmission lines. II. Application of closing control device for high-speed autoreclosing on BC Hydro 500 kV transmission lineIEEE Transactions on Power Delivery, 1997
- Elimination of closing resistors on EHV circuit breakersIEEE Transactions on Power Delivery, 1988