Wavelet transform approach to high impedance fault detection in MV networks
- 1 June 2005
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 1-7
Abstract
Application of wavelet transform technique to high impedance arcing fault detection in distribution networks is presented. Phase displacement between discrete wavelet coefficients calculated for zero sequence voltage and current signals at natural network frequency is tracked. The developed wavelet based HIF detector has been tested with EMTP-ATP generated signals, proving better performance than traditionally used algorithms and methods. The protection method proposed is efficient, robust and may be used for HIF detection independently of the network neutral point grounding mode.Keywords
This publication has 6 references indexed in Scilit:
- A novel technique for high impedance fault identificationIEEE Transactions on Power Delivery, 1998
- Fault location using waveletsIEEE Transactions on Power Delivery, 1998
- Wavelets: a new tool for the resonant grounded power distribution systems relayingIEEE Transactions on Power Delivery, 1996
- Digital simulation of fault arcs in power systemsEuropean Transactions on Electrical Power, 1991
- High impedance fault arcing on sandy soil in 15 kV distribution feeders: contributions to the evaluation of the low frequency spectrumIEEE Transactions on Power Delivery, 1990
- Harmonic behavior during arcing faults on power distribution feedersElectric Power Systems Research, 1988