A new power sensitivity method of ranking branch outage contingencies for voltage collapse

Authors:

Abstract
The objective of this paper is to present a powerful procedure for identifying severe single branch outage contingencies with respect to saddle-mode bifurcation induced voltage collapse, given a power system operating point, a load demand forecast, and a generation dispatch. The new power sensitivity ranking algorithm for voltage collapse, called /spl lambda//MVA sensitivity, provides more accurate "distance to collapse" estimates than linear admittance sensitivity, yet requires only slightly more computation time. The distinguishing features are the ability (1) to rank all branches in a large-scale power system quickly, and (2) to estimate the outage contingency bifurcation values accurately. As an illustration, the new /spl lambda//MVA sensitivity ranking algorithm can estimate all 6689 single branch outage contingency bifurcation points (/spl lambda/*/sub ctgc/) of a 3493 bus power system within 3% relative error, except for two branches within 7%, in less than 4 min on a 180 MHz PentiumPro PC.

This publication has 16 references indexed in Scilit: