An analytical model of a single phase DQ-controlled inverter for power system short circuit calculations
Authors:
- 21 November 2016
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 1-5
Abstract
The short-circuit contribution of Inverter interfaced systems is determined by the control architecture, generally limited to 110%–150% of rated current and is generally not sustained past a cycle or two. IEEE1574 compliant inverters with anti-islanding may trip without contributing to a fault. However, as technology moves towards ride-through for remote faults, the modeling of these inverters becomes important. Based on reasonable approximations of the controller response we derive a simple yet accurate analytical model for the fault contribution of a single phase dq-controlled inverter. The derived model is compatible with typical fault calculation programs.Keywords
This publication has 6 references indexed in Scilit:
- Interpreting the short circuit behavior of Type 4 wind turbine generator2014
- Fault models of inverter-interfaced distributed generators: Experimental verification and application to fault analysis2011
- Grid Converters for Photovoltaic and Wind Power Systems2010
- Understanding Fault Characteristics of Inverter-Based Distributed Energy Resources2010
- Study and Development of Anti-Islanding Control for Grid-Connected Inverters2004
- Dynamic stability of grid-connected photovoltaic systems2004