Impulse Grounding Resistance Reduction Measures for Transmission Line Towers in Desert, Gobi, and Barren Land Regions
Open Access
Abstract
The high soil resistivity in desert, Gobi, and barren land regions limits the lightning current dissipation capability of conventional needle-type grounding electrodes, thereby increasing the lightning-related risk to transmission lines. To address this issue, a three-dimensional transient simulation model of a horizontal needle-type grounding electrode equipped with grounding modules was developed in COMSOL Multiphysics (version 6.2) based on electromagnetic field theory and the nonlinear ionization characteristics of soil. The effects of the number, spacing, and downward inclination angle of the needles, as well as the geometric dimensions of the grounding modules, on the impulse grounding resistance and current dissipation characteristics were systematically investigated. The simulation results indicate that the needle-tip effect and mutual shielding effect between adjacent needles are the primary factors governing current dissipation performance. Increasing the number and spacing of the needles improves the grounding performance. Among the discrete inclination angles investigated, intermediate inclination angles generally exhibited relatively low impulse grounding resistance; however, the differences among the inclination angles were small, and the inclination angle corresponding to the minimum impulse grounding resistance varied with the critical soil ionization field strength. Under the baseline conditions of a 10 kA impulse current and an initial soil resistivity of 1000 Ω·m, the resistance reduction provided by the grounding modules decreased from 15.34% for one bilateral needle unit to 12.62% for nine units. Increasing the needle spacing from 0.3 to 1.1 m reduced the impulse grounding resistance by 18.09% and 11.38% for the configurations with and without grounding modules, respectively. Increasing the module radius from 0 to 0.25 m produced a 29.03% reduction in impulse grounding resistance, although the incremental resistance-reduction benefit gradually diminished as the module dimensions increased. These findings provide a theoretical reference for optimizing transmission-line tower grounding systems in high-resistivity desert, Gobi, and barren land regions.Keywords
This publication has 27 references indexed in Scilit:
- Investigation of soil resistivity impacts on the electrodes of grounding system subjected to lightning strikesIET Generation, Transmission & Distribution, 2024
- Experimental characterization of contact resistance of desert soil with waste-enhancement materials in grounding systemsResults in Engineering, 2024
- Experimental analysis of horizontal grounding wires buried in high-resistivity soils subjected to impulse currentsElectric Power Systems Research, 2022
- Modeling soil ionization effect based on experimental dataElectric Power Systems Research, 2022
- A simplified numerical modeling of the transient behavior of grounding systems considering soil ionizationElectric Power Systems Research, 2022
- Soil impulse ionisation model based on dynamic changes of electric fieldIET Science, Measurement & Technology, 2022
- A study of grounding arrangements composed by vertical electrodes for two-layered stratified soil modelsElectric Power Systems Research, 2020
- An improved model for soil ionization around grounding system and its application to stratified soilJournal of Electrostatics, 2004
- The soil ionization gradient associated with discharge of high currents into concentrated electrodesIEEE Transactions on Power Delivery, 1994