CFD Assessment of Car Park Ventilation System in Case of Fire Event
Open Access
- 11 September 2023
- journal article
- research article
- Published by MDPI AG in Applied Sciences
- Vol. 13 (18) , 10190
Abstract
This scientific article presents the results of computational fluid dynamics (CFD) simulations conducted using OpenFOAM to evaluate the effectiveness of a jet fan ventilation system in managing the dispersion of smoke resulting from a car fire incident within an underground car park spanning a total area of 21,670 m2, situated in Tabriz, Iran. The primary objective of the study is to determine the velocity fields and evaluate visibility conditions within a 10 m radius to gauge the efficiency and effectiveness of the system. The study employs a smoke concentration production rate of 5.49 × 10−4 kg/m3s for simulations involving fire scenarios. A total of 17 fire scenarios are examined, each extending 30 m in all directions from the initial location. The research findings demonstrate that the placement of jet fan components plays a significant role in the system’s efficiency, with fans positioned near the ceiling leading to back-layering. To mitigate this issue, the recommended design solution involves the strategic installation of multiple jet fan arrays in specific zones with the addition of 10 extra jet fans, effectively curbing lateral smoke dispersion. Furthermore, the analysis of air flow rates shows that when jet fans direct an excessive airflow towards the exhaust shafts (which have a designated flow rate of 22.5 m3/s), recirculating flows occur, leading to the dispersion of smoke throughout the car park. Consequently, the utilization of low-velocity jet fans (11.2 m/s) proves to be more effective in clearing smoke compared to high-velocity jet fans (22.3 m/s). The study also emphasizes the importance of optimal positioning of supply and exhaust shafts to achieve effective smoke control, highlighting the need for placing them on opposite walls or minimizing airflow turns. Additionally, the research underscores the significance of fire resistance in jet fan units, as their failure during fire incidents can have severe consequences.Keywords
This publication has 29 references indexed in Scilit:
- Energy Efficient Tunnel SolutionsTransportation Research Procedia, 2016
- CFD optimization of jet fan ventilation in a car park by fractional factorial designs and response surface methodologyBuilding Simulation, 2015
- CFD Analysis of Smoke and Temperature Control System of an Indoor Parking Lot with Jet FansJournal of Thermal Engineering, 2015
- Smoke control in case of fire in a large car park: CFD simulations of full-scale configurationsFire Safety Journal, 2013
- Numerical modelling of industrial indoor environments: A comparison between different turbulence models and supply systems supported by field measurementsBuilding and Environment, 2011
- Numerical Study on Impulse Ventilation for Smoke Control in an Underground Car ParkProcedia Engineering, 2011
- Fluid Flow Equations2002
- Ventilation design: Use of computational fluid dynamics as a study toolBuilding Services Engineering Research & Technology, 1995
- Two-equation eddy-viscosity turbulence models for engineering applicationsAIAA Journal, 1994
- Numerical Calculation of Time-Dependent Viscous Incompressible Flow of Fluid with Free SurfaceThe Physics of Fluids, 1965