Abstract
Overheated electrical joints due to loose connection are often precursors of electric fires, arc faults, and arc flash in electrical systems. This paper is about the formation mechanism and behavior characteristics of loose connection induced overheated electrical joints. Specific experiments were conducted on busbar joints and systems with currents ranging from 100 A up to 5000 A. The lead time of the overheated contact formation is significantly impacted by the tightening torque of busbar bolts, the amplitude of current, and the proper sizing of electrical joints.Keywords
This publication has 11 references indexed in Scilit:
- Application Feasibility of Detecting Glowing Contacts Using Acoustic Sensing Technology2009
- Thermal Model of Electrical Contacts Based on Experimental Data2008
- Material Effect on Glowing Contact Properties2007
- Characterization of Glowing Contacts using Optical Emission Spectroscopy2007
- Electrical Contacts Condition Diagnostics Based on Wireless Temperature Monitoring of Energized Equipment2006
- Glowing Contact Physics2006
- Degradation of power contacts in industrial atmosphere: silver corrosion and whiskers2003
- Evaluation of receptacle connections and contacts2002
- Glowing contact areas in loose copper wire connectionsIEEE Transactions on Components, Hybrids, and Manufacturing Technology, 1992
- Failure of aluminum connections in residential applications1991