Measurement of the resistive leakage current in surge arresters under artificial rain test and impulse voltage subjection
- 8 May 2009
- journal article
- Published by Institution of Engineering and Technology (IET) in IET Science, Measurement & Technology
- Vol. 3 (3) , 256-262
Abstract
Surge arresters are installed on transmission and distribution lines and in substations between phase and earth in order to improve the lightning performance and reduce the failure rates. High-energy stresses and housing deterioration are the main factors of degradation and damage of surge arresters. Thus, there is need for testing and monitoring the electrical network's arresters, in order to verify their good condition and their ability to effectively protect the lines. The most common method used, is the measurement of the arresters' total leakage current (with the isolation of the resistive part), which is an indicator of the arrester's condition, since every change, deterioration or damage leads to an increase of the resistive leakage current. In the current work, the total leakage current of two 20 kV ZnO surge arresters without gaps is measured and the resistive component for three different cases (brand new arresters, measurements under artificial rain and measurements after impulse voltage subjection) is computed. The analysis of the produced results can be useful in correct diagnosis of arresters' condition and in more effective schedule maintenance, since any recorded high-resistive currents do not necessarily result arrester's repair or replacement.Keywords
This publication has 8 references indexed in Scilit:
- Condition Assessment of High Voltage Insulation in Power System Equipment2008
- New Techniques for Field Inspection of Medium Voltage Surge Arresters2007
- Electromagnetic emission based monitoring technique for polymer ZnO surge arrestersIEEE Transactions on Dielectrics and Electrical Insulation, 2006
- Possibilities to reveal internal moisture in polymeric metal oxide surge arresters by means of PD and EMR measurements2003
- Influence of harmonics in system voltage on metal oxide surge arrester diagnostics2003
- Diagnostics and monitoring of metal-oxide surge arresters in high-voltage networks-comparison of existing and newly developed proceduresIEEE Transactions on Power Delivery, 2001
- Pollution performance of 110 kV metal oxide arrestersIEEE Transactions on Power Delivery, 1997
- New method for measurement of the resistive leakage currents of metal-oxide surge arresters in serviceIEEE Transactions on Power Delivery, 1990