A UPFC for Voltage Regulation in LV Distribution Feeders With a DC-Link Ripple Voltage Suppression Technique
- 9 September 2020
- journal article
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industry Applications
- Vol. 56 (6) , 6857-6870
Abstract
The large-scale integration of distributed photovoltaic generation causes several power quality issues in low voltage (LV) distribution networks. Network voltage profile variations severely affect the LV distribution networks. The four-leg unified power flow controller (4L-UPFC) has series and shunt converters that can address the power quality issues. However, instantaneous power theory shows that second-order harmonic voltage (2ωHV) appears at the dc-link capacitor of the 4L-UPFC during any unbalanced operations. This article proposes control strategies for series and shunt converters that will simultaneously regulate the load voltages of a distribution feeder while suppressing the 2ωHV term on the dc-link of the UPFC. A controlled negative sequence current from the shunt converter is used to suppress the 2ωHV term on the dc-link. The active suppression of the 2ωHV term allows electrolytic capacitors to be replaced with small long life ceramic or film capacitors, and this does not require additional passive compensation. Stability analysis of the control loops demonstrates the overall stability of the converter system. The proposed control methods have been implemented on a Texas DSP (F28377D). An experimental demonstration on a laboratory scale prototype shows that the proposed control methods can effectively regulate the load voltages at LV distribution feeders and suppress the 2ωHV on the dc-link of UPFC during unbalanced loads and supply conditions.Keywords
Funding Information
- Australian Government
This publication has 39 references indexed in Scilit:
- A review of high PV penetrations in LV distribution networks: Present status, impacts and mitigation measuresRenewable and Sustainable Energy Reviews, 2016
- Optimal Operation of Distributed Energy Storage Systems to Improve Distribution Network Load and Generation Hosting CapabilityIEEE Transactions on Sustainable Energy, 2015
- DC-Bus Voltage Regulation for a DC Distribution System With a Single-Phase Bidirectional InverterIEEE Journal of Emerging and Selected Topics in Power Electronics, 2015
- Full-State Feedback Equivalent Controller for Active Damping in $LCL$-Filtered Grid-Connected Inverters Using a Reduced Number of SensorsIEEE Transactions on Industrial Electronics, 2015
- DC-Link Capacitance Minimization in T-Type Three-Level AC/DC/AC PWM ConvertersIEEE Transactions on Industrial Electronics, 2014
- Distribution level SiC FACTS devices with reduced DC bus capacitance for improved load capability and solar integration2014
- Comparative evaluation of passive damping topologies for parallel grid-connected converters with LCL filters2014
- DC-Link Voltage Stabilization for Reduced DC-Link Capacitor InverterIEEE Transactions on Industry Applications, 2013
- Dual current control scheme for PWM converter under unbalanced input voltage conditionsIEEE Transactions on Industrial Electronics, 1999
- Regulation of a PWM rectifier in the unbalanced network state using a generalized modelIEEE Transactions on Power Electronics, 1996