Dynamic equivalent model of doubly fed wind farm during electromagnetic transient process
Authors:
Open Access
- 8 September 2016
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in IET Renewable Power Generation
- Vol. 11 (1) , 100-106
Abstract
The dynamic processes of a power system during grid fault are being changed by the large‐scale applications of wind generation. The transient characteristics of a single doubly fed induction generator (DFIG) have been widely researched. However, the overall characteristics of a wind farm have not been obtained because the existing models of a wind farm cannot cover the differences caused by normal instruction values, controller responses, and protections of the DFIGs. The equivalent model of a doubly fed wind farm used for the electromagnetic transient analysis is studied. The feature information of the stator short‐circuit current (SCC) of a DFIG was excavated based on transient behaviour analysis. The structure similarity indices are established to evaluate the envelope curves of the SCCs. A clustering method based on transient physical process is then proposed to distinguish coherent DFIGs. The equivalent model represented by a small number of DFIGs is obtained by aggregating coherent groups. The simulations indicate that the method effectively recognises transient state differences of the DFIGs. Thus, the model meets the requirements of the transient analysis.Keywords
Funding Information
- National Natural Science Foundation of China (51407017)
- Chongqing Research Program of Basic Research and Frontier Technology (cstc2015jcyjA90016)
- Fundamental Research Funds for the Central Universities (106112015CDJXY150001)
This publication has 10 references indexed in Scilit:
- Understanding the Doubly Fed Induction Generator During Voltage DipsIEEE Transactions on Energy Conversion, 2012
- Cluster analysis of wind turbines of large wind farm with diffusion distance methodIET Renewable Power Generation, 2011
- A review on scale and siting of wind farms in ChinaWind Energy, 2010
- Wind farm and wake effect modeling for simulation of a studied power system2009
- Aggregated dynamic model for wind farms with doubly fed induction generator wind turbinesRenewable Energy, 2008
- Dynamic Behavior of the Doubly Fed Induction Generator During Three-Phase Voltage DipsIEEE Transactions on Energy Conversion, 2007
- Short-Circuit Current of Wind Turbines With Doubly Fed Induction GeneratorIEEE Transactions on Energy Conversion, 2007
- Two Alternative Modeling Approaches for the Evaluation of Wind Farm Active and Reactive Power PerformancesIEEE Transactions on Energy Conversion, 2006
- General model for representing variable speed wind turbines in power system dynamics simulationsIEEE Transactions on Power Systems, 2003
- Doubly fed induction generator usingback-to-back PWM convertersand its application to variable-speed wind-energy generationIEE Proceedings - Electric Power Applications, 1996