An Experimental Study for Deriving Fire Risk Evaluation Factors for Cables in Utility Tunnels
Open Access
Abstract
In this study, we performed three tests to measure the fire-retardant performance of power cables installed in utility tunnels. The standards we applied for testing are ISO 5660-1, NES 713, and IEEE 1202. Specifically, we performed a cone calorimetric analysis, calculated the toxicity index, and measured the flame spread length on material surfaces. Even though the same fire-retardant chemical composites were applied, various differences in fire-retardant performance were found depending on the chemical properties of the cable sheath and insulation. We also found that gaseous substances generated during the burning of cables can serve as important risk assessment factors in fires. We determined that, in addition to the heat generated when the cable burns, the toxic gases emitted at this time can also be a risk factor. This is because it is important to consider any potential risk to a person entering as part of an initial response to an event or accident involving cables installed in utility tunnels. Moreover, in the event of a fire in the cable, there is a risk of hazardous substances flowing into the city center as toxic gases are released. Therefore, we determined that the risk of hazardous gases emitted during cable fire should be reflected in the fire-retardant performance standard.Keywords
Funding Information
- Korea government (MSIT, MOIS, MOLIT, and MOTIE) (2020-0-00061)
This publication has 13 references indexed in Scilit:
- Automatic Data Generation Method for Precise Ceiling Temperature Prediction of Cables Fire in the Utility Tunnel and Full-Scale Experimental VerificationFire Technology, 2022
- Estimating the two-dimensional thermal environment generated by strong fire plumes in an urban utility tunnelProcess Safety and Environmental Protection, 2021
- Experimental study on the fire shape and maximum temperature beneath ceiling centerline in utility tunnel under the effect of curved sidewallTunnelling and Underground Space Technology, 2020
- Investigation into the toxicity of combustion products for CR/EPR cables based on aging periodJournal of Mechanical Science and Technology, 2020
- An Experimental Study on the Combustion Characteristics of Non Class 1E CablesJournal of the Korean Society of Combustion, 2019
- A Study on the Human Toxicity of Combustion Products for Non Class 1E CablesJournal of the Korean Society of Hazard Mitigation, 2018
- Hazard Assessment of Combustion Gases from Interior MaterialsFire Science and Engineering, 2015
- Study on the Fire Risk Prediction Assessment due to Deterioration contact of combustible cables in Underground Common Utility TunnelsJournal of The Korean Society of Disaster Information, 2015
- IEEE 1202 flame testing of cables for use in cable tray2002
- Flame retardancy of polyamide 11 with a decabromodiphenyl-antimony trioxide mixture. A bromine-antimony-nitrogen synergismPolymer Degradation and Stability, 1990