Equipment failures caused by power quality disturbances
Authors:
- D. DivanDDD. Divan
- W. KranzWKW. Kranz
- W. BrumsickleWBW. Brumsickle
- 8 November 2004
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- Vol. 1 (01972618) , 482-489
Abstract
This paper provides insight into a failure mechanism that impacts a broad range of industrial equipment. Voltage surges have often been blamed for unexplained equipment failure in the field. Extensive voltage monitoring data suggests that voltage sags occur much more frequently than voltage surges, and that current surges that accompany voltage sag recovery may be the actual culprit causing equipment damage. A serious limitation in equipment specification is highlighted, pointing to what is possibly the root-cause for a large percentage of unexplained equipment field failures. This paper also outlines the need for a standard governing the behavior of equipment under voltage sags, and suggests solutions to protect existing equipment in the field.Keywords
This publication has 10 references indexed in Scilit:
- A Grid Information Resource for Nationwide Real-Time Power MonitoringIEEE Transactions on Industry Applications, 2004
- Pilot evaluation of electricity-reliability and power-quality monitoring in California's Silicon Valley with the I-Grid(R) system2004
- Operational experience with a nationwide power quality and reliability monitoring system2004
- Inrush current control for equipment powered by UPSs2003
- Distribution system voltage sags: interaction with motor and drive loads2002
- Effects of unsymmetrical voltage sag types E, F and G on induction motors2002
- Behavior of induction motor due to voltage sags and short interruptionsIEEE Transactions on Power Delivery, 2002
- Dynamic sag correctors: cost-effective industrial power line conditioningIEEE Transactions on Industry Applications, 2001
- Control and performance of a pulse-density-modulated series-resonant inverter for corona discharge processesIEEE Transactions on Industry Applications, 1999
- Canadian national power quality survey: frequency and duration of voltage sags and surges at industrial sitesIEEE Transactions on Industry Applications, 1998