A Stator Internal Short-Circuit Fault Protection Method for Turbo-Generator Based on Instantaneous Power Oscillation Ratio
- 16 January 2023
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Energy Conversion
- Vol. 38 (3) , 1903-1912
Abstract
For large turbo-generators, the longitudinal differential protection can only reflect the stator internal inter-phase short-circuit fault, and cannot reflect the inter-turn short-circuit fault. The protection methods for inter-turn short-circuit faults have the problem of low sensitivity, such as the longitudinal zero-sequence voltage protection and the negative sequence component-based protection. Therefore, a stator internal short-circuit fault protection method for turbo-generator based on instantaneous power oscillation ratio (IPOR) is proposed in this paper. The instantaneous power variation of the generator before and after the fault is analyzed, and the IPOR is calculated by using the balanced power component and the oscillatory power component. Then, the method to judge whether the generator has an internal short-circuit fault based on the amplitude and phase of IPOR is proposed. The experimental results verify the effectiveness of the proposed protection method, which has a high sensitivity to the inter-turn short-circuit faults with a small turn difference. The protection is stable and does not malfunction during the system oscillation. In addition, the action time of the protection method does not exceed 1.5 power frequency cycles under various working conditions, which can meet the speed requirements of generator protection.Keywords
Funding Information
- Fundamental Research Funds for the Central Universities (YCJJ202202020)
- National Natural Science Foundation of China (51877089)
This publication has 25 references indexed in Scilit:
- Diagnosis of interturn fault in stator winding of turbo‐generatorInternational Transactions on Electrical Energy Systems, 2019
- Integral-based stabilization of generator differential protectionInternational Journal of Electrical Power & Energy Systems, 2019
- A New Internal Fault Detection and Classification Technique for Synchronous GeneratorIEEE Transactions on Power Delivery, 2018
- A novel protection scheme for synchronous generator stator windings based on SVMProtection and Control of Modern Power Systems, 2017
- Improved Model of Synchronous Generators Internal Faults Based on Circuit-Coupled FEMIEEE Transactions on Energy Conversion, 2017
- Control of DFIG Wind Power Generators in Unbalanced Microgrids Based on Instantaneous Power TheoryIEEE Transactions on Smart Grid, 2016
- A Novel Method Based on Fuzzy Logic and Data Mining for Synchronous Generator Digital ProtectionIEEE Transactions on Power Delivery, 2014
- Studies on the Stator Single-Phase-to-Ground Fault Protection for a High-Voltage Cable-Wound GeneratorIEEE Transactions on Energy Conversion, 2013
- Operating characteristics of constant-pressure compressed air energy storage (CAES) system combined with pumped hydro storage based on energy and exergy analysisEnergy, 2011
- Differential Protection Based on Zero-Sequence Voltages for Generator Stator Ground FaultIEEE Transactions on Power Delivery, 2006