The determination of FFA concentration in transformer oil by fluorescence measurements
Authors:
- R. BlueRBR. Blue
- D. UttamchandaniDUD. Uttamchandani
- O. FarishOFO. Farish
- 1 January 1998
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 5 (6) , 892-895
Abstract
Condition monitoring of the paper winding of power transformers involves the measurement of the concentration of 2-furaldehyde, also called furfuraldehyde (FFA) in the transformer oil. Measuring the concentration of FFA in the oil gives a reliable indication of the condition of the paper insulation. This measurement has routinely been performed by using techniques such as high performance liquid chromatography. We report for the first time the use of fluorescence-based methods for the assessment of FFA in transformer oiKeywords
This publication has 2 references indexed in Scilit:
- Portable optoelectronic instrument formeasuring furfuraldehyde intransformer oilIEE Proceedings - Science, Measurement and Technology, 1998
- A novel solid-state material for furfuraldehyde detectionIEEE Transactions on Dielectrics and Electrical Insulation, 1997