Analysis of Multistress-Accelerated Aged Stator Bars Using a Three-Phase Test Arrangement
Authors:
- 21 February 2006
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Energy Conversion
- Vol. 21 (1) , 162-170
Abstract
The aging characteristics of stator bars, which have been subjected to accelerated aging tests in a three-phase model stator under simultaneously applied electrical, mechanical, and thermal stresses, have been evaluated using diagnostic test procedures. The ac breakdown test has been found to be the most effective means for assessing the extent of aging undergone by the stator bars. The results indicate that under multistress conditions relatively small increases in the magnitudes of the stress acceleration factors are sufficient to lead to significant increases in the aging rate of the insulating systems of stator bars.Keywords
This publication has 21 references indexed in Scilit:
- Multi-Stress Aging of Stator Bars With Electrical, Thermal, and Mechanical Stresses as Simultaneous Acceleration FactorsIEEE Transactions on Energy Conversion, 2004
- A three-phase multi-stress accelerated electrical aging test facility for stator barsIEEE Transactions on Energy Conversion, 2000
- Analysis of in-service aged stator barsIEEE Transactions on Energy Conversion, 1995
- Multiple stress aging of solid-dielectric extruded dry-cured insulation systems for power transmission cablesIEEE Transactions on Power Delivery, 1994
- Spark-to-glow discharge transition due to increased surface conductivity on epoxy resin specimensIEEE Transactions on Electrical Insulation, 1993
- Relationship between partial discharge pulse height analysis and subsequent voltage endurance of stator bars and coilsIEEE Transactions on Energy Conversion, 1992
- Assessment of insulation condition in rotating machine statorsIEEE Transactions on Energy Conversion, 1992
- A thermal cycling type test for generator stator winding insulationIEEE Transactions on Energy Conversion, 1991
- AC breakdown characteristics of in-service aged XLPE distribution cablesIEEE Transactions on Power Delivery, 1988
- The ability of diagnostic tests to estimate the remaining life of stator insulationIEEE Transactions on Energy Conversion, 1988