Abstract
The self-balanced loading test is a state-of-art pile testing method, but its suitability to pile bearing capacity determination in transformer substation engineering in mountainous and hilly areas is not yet clear. In this study, a two-dimensional axisymmetric numerical model is established by the PLAXIS software to simulate the behavior and bearing mechanism of shallow rock-socketed short piles based on the self-balanced loading test. The model is first validated by simulating the field tests of two adjacent piles under self-balanced loading. Then the influence factors of the load-displacement curves of piles are analyzed. Thereafter, the mechanical mechanism of the self-balanced loading tests is simulated and compared with the conventional static loading tests. It is observed that the rock modulus, rock-socketed depth of piles, and burial depth of the Osterberg Cell affect the load-displacement significantly, but the cohesion of the rocks affects little. Moreover, compared with the conventional static loading tests, the shear stress of the pile-soil interface distributes less uniformly under self-balanced loading conditions. On this basis, a bearing capacity computation method of shallow rock-socketed short piles based on the self-balanced loading test is proposed.
Funding Information
  • Scientific Research Project of Anhui Provincial Education Department (KJ2021ZD0066, 51608005, SGAHJYJSXLJS1800417)
  • National Natural Science Foundation of China (KJ2021ZD0066, 51608005, SGAHJYJSXLJS1800417)
  • State Grid Anhui Electric Power Co., Ltd. Construction Company (KJ2021ZD0066, 51608005, SGAHJYJSXLJS1800417)

This publication has 21 references indexed in Scilit: