Simulation calculation of 3D electric field and natural flashover analysis of ice‐covered silicone rubber insulator
Authors:
Open Access
- 27 December 2022
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 17 (5) , 1166-1178
Abstract
The effects of uneven icing, number of icicles, inclination angle of icicle, ice pallets and arc ignition on the electric field are ignored for the two‐dimensional axisymmetric model of ice‐covered insulator. Therefore, a 3D simulation model was developed in this paper. The average electric field strength of air gap ( E av ) and maximum field strength of icicle tip ( E max ) were determined to characterize the influence of various factors on the electric field distortion degree. The results show that compared with the insulator without ice and with a dry ice, the supply voltage is almost entirely applied to all icicle air gaps for a wet ice‐covered insulator. E av is independent of icicle diameter and icicle number but increases with the increment of icicle length and icicle inclination angle. E max raises with the increase of icicle length, icicle number, icicle inclination angle and icicle diameter. As the source of electric field distortion, the ice pallets on the surface of the sheds rise the field strength of air gap. Based on the simulation analysis and natural icing test, the applied voltage is redistributed in the remaining air gaps when an arc occurs in the gap near the high‐voltage terminal, thereby causing the subsequent flashover.Keywords
Funding Information
- National Natural Science Foundation of China (51907109, 52107142)
This publication has 27 references indexed in Scilit:
- DC flashover performance of ice‐covered insulators under complex ambient conditionsIET Generation, Transmission & Distribution, 2016
- Crystallisation effect of conductive ions in freezing water during phase transition and its effect on ice flashover voltageIET Generation, Transmission & Distribution, 2016
- Empirical flashover model of EHV post insulators based on ISP parameter in cold environmentsIEEE Transactions on Dielectrics and Electrical Insulation, 2016
- Influence of shed configuration on icing characteristics and flashover performance of 220 kV composite insulatorsIEEE Transactions on Dielectrics and Electrical Insulation, 2016
- Electrical performance of 330-kV composite insulators with different shed configurations under icing conditionsIEEE Transactions on Dielectrics and Electrical Insulation, 2015
- Effect of grading ring on ice characteristics and flashover performance of 220 kVcomposite insulators with different shed configurationsIEEE Transactions on Dielectrics and Electrical Insulation, 2015
- Dimensioning of booster sheds for icing protection of post station insulatorsIEEE Transactions on Dielectrics and Electrical Insulation, 2014
- Effects of electric field distribution on icing and flashover performance of 220 kV composite insulatorsIEEE Transactions on Dielectrics and Electrical Insulation, 2014
- Three-Dimensional Modeling of Potential and Electric-Field Distributions Along an EHV Ceramic Post Insulator Covered With Ice—Part I: Simulations of a Melting PeriodIEEE Transactions on Power Delivery, 2005