Grounding Faulted Feeder Detection Methods Applied in Chinese Ineffectively Earthed Distribution Systems
Authors:
- 1 September 2007
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- No. 01972618,p. 1348-1352
Abstract
Medium voltage (MV) power systems have been operated with floating neutral or Petersen-coil grounded. Grounding fault current is no more than ten amperes. Traditional grounding faulted feeder detection methods based on zero sequence current have poor sensitivity in this case. In the last ten years, many novel faulted feeder detection methods have been developed in China. Some of them have widely and successfully applied in Chinese distribution systems. Four best of them (Harmonic currents comparison based fault detection, signal injection based detection, traveling wave based detection, and phase current difference based detection) are presented in the paper. The advantage and disadvantage of each method are analyzed, and problems that need further study are also brought forward.Keywords
This publication has 12 references indexed in Scilit:
- Evaluation of Feeder Monitoring Parameters for Incipient Fault Detection Using Laplace Trend StatisticIEEE Transactions on Industry Applications, 2004
- Grounding and Ground Fault Protection of Multiple Generator Installations on Medium-Voltage Industrial and Commercial Power Systems—Part 3: Protection Methods Working Group ReportIEEE Transactions on Industry Applications, 2004
- Equivalent circuit application to a phase to ground fault detection in distribution networks without MV voltage measurements2004
- An efficient treatment of transient residual currents in distribution networks grounded with Petersen coil2004
- On-site safety evaluation for earth fault in mining power systemsIEEE Transactions on Industry Applications, 2003
- Ground fault protection for 6... 10 kV distribution system2002
- Location strategies and evaluation of detection algorithms for earth faults in compensated MV distribution systemsIEEE Transactions on Power Delivery, 2000
- Arcing fault detection in underground distribution networks-feasibility studyIEEE Transactions on Industry Applications, 2000
- A new deal for safety and quality on MV networksIEEE Transactions on Power Delivery, 1997
- An overview of fault monitoring and diagnosis in mining equipmentIEEE Transactions on Industry Applications, 1994