Abstract
This paper presents a novel data driven framework based on Support Vector Regression to reduce the bandwidth requirement for transmission of Phasor Measurement Unit (PMU) data. This is achieved by judicious elimination of redundant data at the PMU before transmission. Simultaneously, the missing samples are predicted at PDC to ensure faithful identification of impending disturbances in the power system. Due to inherent non-stationary nature of PMU data, the hyper-parameters are dynamically recomputed as necessary, thereby maintaining the accuracy of prediction and robustness of the algorithm. Performance of the proposed algorithm is evaluated via large scale simulations using powerline frequency data. A trade-off between prediction quality and runtime of the algorithm is observed, which is addressed by suitable selection of hyper-parameters. Compared to the competitive data reduction scheme, the proposed algorithm saves around 60% bandwidth and identifies power system disturbances 73% more accurately.