CES peak demand shaving with energy storage system
Authors:
- 1 October 2017
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 1124-1126
Abstract
This paper analyzes energy cost reduction from peak demand shaving when a CES provider adopts ESS for the CHP-based CES microgrid site in Seoul, Korea. The simulation results show that about 9% of peak shaving can be realized when a 270kWh ESS is used for three thousand CES households. When two or three ESSs are adopted, peak demand shaving increases at most into 12% or 14%, which concludes that ESS capacity enlargement is not so helpful for the peak reduction. It also concludes that peak shaving is appropriate as a supplementary usage of ESS considering that ESS is required to work only a few days for a year to achieve peak shaving.Keywords
This publication has 4 references indexed in Scilit:
- Energy storage systems providing primary reserve and peak shaving in small isolated power systems: An economic assessmentInternational Journal of Electrical Power & Energy Systems, 2013
- Battery storage system for residential electricity peak demand shavingEnergy and Buildings, 2012
- Power systems’ optimal peak-shaving applying secondary storageElectric Power Systems Research, 2012
- Energy peak shaving with local storageSustainable Computing: Informatics and Systems, 2011