Fault Location Scheme for Abnormal Grounding Point in Isolated Ground Wire of Large-Scale Clean Energy Transmission
Authors:
Open Access
- 16 July 2021
- journal article
- research article
- Published by Frontiers Media SA in Frontiers in Energy Research
- Vol. 9
Abstract
There is a large number of grounding switches along the isolated ground wire for the de-icing in the large-scale wind farm. If any of these grounding switches are left open by accident, this can create an unexpected abnormal grounding point in the isolated ground wire. Based on the analysis of the output power of de-icing devices, the output power of different poles can be applied for the abnormal grounding point fault location. Since the rise of output current to the rated current of de-icing devices requires a long time to build up, the protective relay may lock the de-icing device before the output current reaches the rated current. Thus, the ratio of output energy of two poles can be selected to locate the abnormal grounding point. This study verified this location method by conducting a large number of simulations.Keywords
Funding Information
- China Southern Power Grid
This publication has 6 references indexed in Scilit:
- Single Pole-to-Ground Fault Location System for MMC-HVDC Transmission Lines Based on Active Pulse and CEEMDANIEEE Access, 2021
- Single-Line-to-Ground Fault Location in Resonant Grounded Systems Based on Fault DistortionsIEEE Access, 2021
- Fault Location in Overhead Transmission Lines Based on Magnetic Signatures and on the Extended Kalman FilterIEEE Access, 2021
- Time-Domain Fault-Location Method on HVDC Transmission Lines Under Unsynchronized Two-End Measurement and Uncertain Line ParametersIEEE Transactions on Power Delivery, 2015
- Transient stability risk assessment of power systems incorporating wind farmsJournal of Modern Power Systems and Clean Energy, 2013
- Research and Application of DC De–Icing Technology in China Southern Power GridIEEE Transactions on Power Delivery, 2012