Simulation Analysis of Partial Discharge Detection and Localization of Power Cable Based on ATP-EMTP
Authors:
- 1 May 2020
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 275-279
Abstract
Partial discharge(PD) is an effective method to evaluate the insulation state of power cables. Accurate detection and localization of PD signals in cables can be conducive to detect the early fault of the cables.Where to place the sensor to capture and locate the PD signals is a problem in the cable system that one end of the sheath is grounded and one end the sheath is grounded through the sheath protector. For the purpose of solving this problem, we build a ethylenepropylene rubber insulated(EPR) power cable model in ATP-EMTP and study propagation characteristics of PD signals in cables as well as the coupling effect between the conductor and the sheath of the cables. Then the cable system that one end of the sheath is grounded and one end the sheath is grounded through the sheath protector is built. And the optimal installation position of the sensor is determined by simulation. Based on the above research,the PD signals can be located by using the two-terminal location method.Keywords
This publication has 3 references indexed in Scilit:
- The Problem of the Partial Discharge Sources Enumeration in the HV Devices InsulationInternational Journal of Electrical and Electronic Engineering & Telecommunications, 2019
- Direct Introduction of Semicon Layers in XLPE Cable Model2006
- Parameter Determination for Modeling System Transients—Part II: Insulated Cables IEEE PES Task Force on Data for Modeling System Transients of IEEE PES Working Group on Modeling and Analysis of System Transients Using Digital Simulation (General Systems Subcommittee)IEEE Transactions on Power Delivery, 2005