Ground Fault Protection for Bus-Connected Generators in an Interconnected 13.8-kV System
Author:
- 19 March 2007
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industry Applications
- Vol. 43 (2) , 453-461
Abstract
This paper is based on modifications implemented in the protection and grounding systems of a large paper mill and describes selective ground fault protection for a 13.8-kV system with multiple bus-connected generators, synchronous bus ties, and utility interconnections. The ground fault current in the system is reduced from the existing 3400 A to 500 A, and a hybrid grounding system is implemented for each of the generators. As the ground fault currents are reduced to limit the fault damage, the sensitivity and selectivity of the ground fault protection become important. Directional ground fault relays with coordinating pickup settings are applied to achieve this objective. The new platform for directional elements (numerical relays) drives its performance from sequence impedance measurementsKeywords
This publication has 8 references indexed in Scilit:
- MV Generator Low-Resistance Grounding and Stator Ground Fault DamageIEEE Transactions on Industry Applications, 2004
- Grounding and Ground Fault Protection of Multiple Generator Installations on Medium-Voltage Industrial and Commercial Power Systems—Part 3: Protection Methods Working Group ReportIEEE Transactions on Industry Applications, 2004
- Grounding and Ground Fault Protection of Multiple Generator Installations on Medium-Voltage Industrial and Commercial Power Systems—Part 4: Conclusion and Bibliography Working Group ReportIEEE Transactions on Industry Applications, 2004
- Grounding and Ground Fault Protection of Multiple Generator Installations on Medium-Voltage Industrial and Commercial Systems—Part 2: Grounding Methods Working Group ReportIEEE Transactions on Industry Applications, 2004
- Grounding and Ground Fault Protection of Multiple Generator Installations on Medium-Voltage Industrial and Commercial Power Systems—Part 1: The Problem Defined Working Group ReportIEEE Transactions on Industry Applications, 2004
- The impact of system grounding practices on generator fault damageIEEE Transactions on Industry Applications, 1998
- Charging Current Data for Guesswork-Free Design of High-Resistance Grounded SystemsIEEE Transactions on Industry Applications, 1979