Partial discharge signal propagation characteristics inside the winding of oil-immersed power transformer using the equivalent circuit of winding model in the oil
Authors:
- 16 April 2012
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 19 (2) , 472-480
Abstract
The technical soundness of an oil-immersed power transformer under an operating voltage is evaluated in partial discharge (PD) test of long-duration ac withstand voltage test. To establish clear control criteria for this PD test, it is necessary to study PD propagation characteristics inside the transformer windings. In this paper, an analysis model was constructed using constants in the oil for a 500 kV-class transformer to analytically obtain PD signal propagation characteristics. For this analysis model, a circuit model for high frequencies up to several MHz was used in order to obtain the characteristics of highfrequency PD propagating inside the winding in detail. Using this model, PD propagation characteristics were investigated in terms of the PD occurrence position, measurement position, and front time as parameters. As a result, it emerged that the propagation pattern was determined by the winding constants as viewed from the PD injection position and the terminal conditions. When the charge amount was the same, the steeper the PD signal front time, the higher the peak voltage value was likely to be because the waveform became more oscillatory. Conversely, assuming an actual test using the ERA device (PD detector developed by Electrical Research Association), it was found that the front time had little impact on the charge amount measured because the oscillatory high-frequency components were removed. As with the previous studies, it emerged that the PD signal transmission rate was lowest when a PD occurred between sections and the signal was detected as one significantly damped to a level of several percent depending on the conditions.Keywords
This publication has 8 references indexed in Scilit:
- Partial discharge signal propagation characteristics inside the winding of oil-immersed power transformer - using the three-winding transformer model in airIEEE Transactions on Dielectrics and Electrical Insulation, 2011
- Development of high frequency circuit model for oil-immersed power transformers and its application for lightning surge analysisIEEE Transactions on Dielectrics and Electrical Insulation, 2011
- Partial discharge-induced degradation characteristics of insulating structure constituting oil-immersed power transformersIEEE Transactions on Dielectrics and Electrical Insulation, 2010
- Partial discharge-induced degradation characteristics of oil-impregnated insulating material used in oil-immersed power transformersIEEE Transactions on Dielectrics and Electrical Insulation, 2010
- Cross-equipment Evaluation of Partial Discharge Measurement and Diagnosis Techniques in Electric Power Apparatus for Transmission and DistributionIEEE Transactions on Dielectrics and Electrical Insulation, 2008
- An electric model of gas-insulated shunt reactor and analysis of re-ignition surge voltagesIEEE Transactions on Power Delivery, 1999
- Simplified three-phase transformer model for electromagnetic transient studiesIEEE Transactions on Power Delivery, 1995
- Behavior of Oil Corona and Damage of Transformer InsulationIEEE Transactions on Power Apparatus and Systems, 1971