Abstract
The 2009 International Building Code (IBC) structural integrity provisions include a minimum tensile capacity requirement for simple shear steel connections. An all-bolted single-angle connection has been physically tested and analytically modeled to determine its ability to meet this code requirement. The single-angle connection studied was an ASTM-rated A36 102×76.2×9.53-mm (L4×3×3/8-in.) connection having four A325 19.1-mm-diameter (0.75-in.-diameter) snug tight bolts on each angle leg. This connection’s tensile capacity, calculated by prying equations from the current AISC Steel Construction Manual, does not meet the new IBC requirement. Six full-scale tests were performed. For three tests, a lateral restraint was included to examine the effect of beam restraint on connection tensile capacity. The ultimate tensile failure load of the connection was observed to be three times the value predicted by the current AISC prying equations. Both tensile rupture of the web-framing angle leg and bolt ten...