This paper presents a novel scheme based on error estimation for identification of magnetizing inrush and internal fault conditions in transformers. Because the inrush current is a peaked wave with a dead angle, we can discriminate internal fault current from inrush current by comparing the similarity between the actual wave and two reference waves under two different frequency conditions per half cycle. Experimental results indicate that this technique is effective under different fault conditions, and an operating time of 10-13 ms can be achieved for internal faults in transformers.Keywords
This publication has 4 references indexed in Scilit:
- The analysis of operation characteristic of transformer differential protection based on virtual third harmonic theory2003
- A current-based solution for transformer differential protection. II. Relay description and evaluationIEEE Transactions on Power Delivery, 2002
- A current-based solution for transformer differential protection. I. Problem statementIEEE Transactions on Power Delivery, 2001