Impedance Modeling of Three-Phase Grid-Connected Voltage Source Converters With Frequency-Locked-Loop-Based Synchronization Algorithms
- 19 October 2021
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Electronics
- Vol. 37 (4) , 4511-4525
Abstract
With the increased installation of voltage source converters (VSCs) into the power grid, concerns about resonance/stability issues associated with interactions among converters, and between them and the ac grid is growing. The prevailing method for investigating these issues is the impedance modeling of VSCs, which involves linearizing all their control elements, such as their current control and grid synchronization system among others. In this process, most often a phase-locked loop (PLL) is considered for the grid synchronization of VSCs in the literature. The available options for the grid synchronization, however, are not limited to PLLs; a large number of frequency-locked loops (FLLs) for the grid synchronization of VSCs may also be found in the literature. The impedance modeling of three-phase VSCs equipped with FLL-based grid synchronization systems can be quite challenging as FLLs have different structures compared to PLLs. This article aims to address this difficulty. The general idea is obtaining the PLL counterparts of FLLs, which makes the VSC impedance modeling very straightforward. To make this idea clear, several case studies are presented and investigated.Keywords
Funding Information
- Deanship of Scientific Research
- King Abdulaziz University (FP-149-43)
- VILLUM FONDEN under the VILLUM (25920)
- Center for Research on Microgrids
This publication has 34 references indexed in Scilit:
- Understanding the Origin of Oscillatory Phenomena Observed Between Wind Farms and HVdc SystemsIEEE Journal of Emerging and Selected Topics in Power Electronics, 2016
- A Modified Sequence-Domain Impedance Definition and Its Equivalence to the dq-Domain Impedance Definition for the Stability Analysis of AC Power Electronic SystemsIEEE Journal of Emerging and Selected Topics in Power Electronics, 2016
- Three-Phase PLLs: A Review of Recent AdvancesIEEE Transactions on Power Electronics, 2016
- Couplings in Phase Domain Impedance Modelling of Grid-Connected ConvertersIEEE Transactions on Power Electronics, 2016
- Analysis of D-Q Small-Signal Impedance of Grid-Tied InvertersIEEE Transactions on Power Electronics, 2015
- Simple synchronisation technique for three‐phase grid‐connected distributed generation systemsIET Renewable Power Generation, 2013
- An algorithm and implementation system for measuring impedance in the D-Q domain2011
- Frequency-adaptive voltage sequence estimation for grid synchronisationElectronics Letters, 2010
- Synchronisation methods for grid-connected voltage source convertersIEE Proceedings - Generation, Transmission and Distribution, 2001
- A frequency scanning method for the identification of harmonic instabilities in HVDC systemsIEEE Transactions on Power Delivery, 1995