Sheath Voltages and Currents in 230kV Oil-Filled Underground Power Cables
Authors:
- 1 August 2015
- journal article
- Published by Trans Tech Publications, Ltd. in Applied Mechanics and Materials
- Vol. 781, 276-279
Abstract
Three-phase underground power cables can induce voltages and currents in their recover sheaths. The induced voltages and currents in sheath are undesirable. They generate heat losses and reduce the cable ampacity. Moreover, the induced voltages can generate electric shock to the workers, who maintain the power cables. It is very important to predict the sheath voltages and currents, which depend on different parameters, such as the sheath grounding system, the geometry of the cables, the gap between them, etc. In this paper, the voltages and currents induced in sheath for different installation of underground power cables (trefoil and flat formation) are studied and presented. For each case study of installation, the results of sheath voltages and currents have been computed and compared. Finally, the case of cross bonding with increasing of cable spans can reduce the sheath voltage significantly.Keywords
This publication has 3 references indexed in Scilit:
- IEEE Guide for Bonding Shields and Sheaths of Single-Conductor Power Cables Rated 5 kV through 500 kV2014
- Minimum voltage rating of sheath voltage limiters in underground cable systems: The influence of corrugated cable sheaths2012
- Transmission capacity design of underground power cables installed in deep tunnel2006