Temperature efficiency of heat exchangers in air handling units
Open Access
- 23 December 2019
- journal article
- Published by Politechnika Koszalinska in Journal of Mechanical and Energy Engineering
- Vol. 3 (3) , 267-272
Abstract
: In order to reduce ventilation heat loss and improve energy efficiency of low-energy buildings air-handling units (AHUs) with heat recovery are used. The article presents results of surveys performed in a passive building located in Katowice concerning the temperature efficiency of heat and cold recovery of two selected AHUs, with different heat exchangers. For this purpose the measurement data from the Building Management System (BMS) for the period 1.08.2015-31.07.2016 were used. The first unit was equipped with a rotary heat exchanger. Its average annual temperature efficiency of heat recovery was 47.2% annually. The efficiency of cold recovery amounted 52.9% on average for the warm half year. The second unit had a cross-flow exchanger. The average annual temperature efficiency of heat recovery in this device was 80.1%. The efficiency of cold recovery amounted 57.2% on average for the warm half year. Additional remarks concerning the temperature measurement in analysed units were also given.Keywords
This publication has 19 references indexed in Scilit:
- Field testing of a novel hybrid solar assisted desiccant evaporative cooling system coupled with a vapour compression heat pumpApplied Thermal Engineering, 2018
- Experimental study on an innovative enthalpy recovery technology based on indirect flash evaporative coolingApplied Thermal Engineering, 2018
- A review on the air-to-air heat and mass exchanger technologies for building applicationsRenewable and Sustainable Energy Reviews, 2017
- Experimental Performance Analyses of a Heat Recovery System for Mechanical Ventilation in BuildingsEnergy Procedia, 2015
- Frost formation in the cross-flow plate heat exchanger for energy recoveryInternational Journal of Heat and Mass Transfer, 2015
- A comprehensive review of heat recovery systems for building applicationsRenewable and Sustainable Energy Reviews, 2015
- Extra cost analyses of two apartment buildings for achieving nearly zero and low energy buildingsEnergy, 2015
- Review of the advances in open-cycle absorption air-conditioning systemsRenewable and Sustainable Energy Reviews, 2013
- Review on heat recovery technologies for building applicationsRenewable and Sustainable Energy Reviews, 2012
- Analytical and experimental analysis of a low-pressure heat exchanger suitable for passive ventilationEnergy and Buildings, 2011