Optimal location of facts devices to enhance power system security
Authors:
- S. GerbexSGS. Gerbex
- R. CherkaouiRCR. Cherkaoui
- A.J. GermondAGA.J. Germond
- 9 July 2004
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- Vol. 3, 61-67
Abstract
This paper compares three heuristic methods (SA, TS and GA) applied to the optimal location of FACTS devices in a power system. The optimizations are made on three parameters: the location of the devices, their types and their sizes. The FACTS devices are located in order to enhance the system security. Five types of FACTS controllers are modeled for steady-state studies: TCSC, TCVR, TCPST, SVC and UPFC. Simulations are performed on an IEEE 118-bus power system for several numbers of devices. Results show that the three algorithms converge to similar optimal solutions. The security margin of the system may be increased with the use of FACTS devices, but some limitations are observed. The locations of the devices and their influence areas are analyzed.Keywords
This publication has 5 references indexed in Scilit:
- Optimal location of multi-type FACTS devices in a power system by means of genetic algorithmsIEEE Transactions on Power Systems, 2001
- Power flow control and power flow studies for systems with FACTS devicesIEEE Transactions on Power Systems, 1998
- Assessment and control of the impact of FACTS devices on power system performanceIEEE Transactions on Power Systems, 1996
- Modern Power Systems Control and Operation1988
- Optimization by Simulated AnnealingScience, 1983