An essential evaluation criterion in the design of SF6-free switchgear is long-term reliability, which is evaluated by a combination of approx. 40 years' experience with gas-insulated switchgear and the simulation of long-term effects. Long-term effects such as the aging of certain material types induced by the insulating gas can be caused by a combination of chemical, thermal, mechanical, and electrical processes. In the early phase of product development such effects were addressed by selecting suitable materials and manufacturing technologies. Furthermore, material and gas aging tests (up to 5 000 hours) were conducted to ensure compatibility. Early pilots confirm the development results. In this way, initial experience of handling in grid-operation could also be gained. In this paper the authors discuss how the combination of aging tests, simulation models and an insightful pilot phase has made it possible to ensure a reliable and long-term operation of F-gas free solutions in the grid.