Experiments and Modeling of Large-scale Benchmark Enclosure Fire Suppression
- 11 August 2009
- journal article
- research article
- Published by SAGE Publications in Journal of Fire Sciences
- Vol. 28 (2) , 109-139
Abstract
This article presents a series of experiments on benchmark fire suppression. The experiments were performed in a controlled environment, utilizing a cylindrical object or calorimeter centered above a 2 m diameter pan filled with kerosene-based hydrocarbon fuel, JP8. The experimental setup and procedure for gathering data on water suppression performance are presented. The characteristics of the nozzles used in the experiments are presented as well. The experimental results provide the boundary condition and temporal data necessary for validation of the fire suppression models used. The article also includes simulation results on the fire suppression experimental tests. The suppression simulations were carried out using a numerical model based on a Temporally Filtered Navier-Stokes (TFNS) formulation coupled with a Lagrangian model for droplets, which includes detailed descriptions of the interaction between the water droplets and the fire plume. The results from both experiments and simulations suggest that the criterion for complete suppression depends on a combination of factors including the mass flow rate (or nozzle diameter), nozzle operating pressure, and calorimeter presence. A critical regime which distinguished the regions of suppression and no-suppression in the domain of the mass flow rate versus operating pressure is found.Keywords
This publication has 27 references indexed in Scilit:
- A computational and experimental study of ultra fine water mist as a total flooding agentFire Safety Journal, 2007
- UNSTEADY RANS MODELING OF WATER-SPRAY SUPPRESSION FOR LARGE-SCALE COMPARTMENT POOL FIRESAtomization and Sprays, 2007
- Extinction of gas and liquid pool fires with water spraysFire Safety Journal, 2003
- A quasi-steady-state model for predicting fire suppression in spaces protected by water mist systemsFire Safety Journal, 2000
- The Effects of Droplet Size and Injection Orientation on Water Mist Suppression of Low and High Boiling Point Liquid Pool FiresCombustion Science and Technology, 2000
- Fire suppression by water spraysProgress in Energy and Combustion Science, 2000
- The Capabilities and Limitations of Total Flooding, Water Mist Fire Suppression Systems in Machinery Space ApplicationsFire Technology, 2000
- Simulation of water mist suppression of small scale methanol liquid pool firesFire Safety Journal, 1999
- A Computational Fluid Dynamic Model of Fire Burning Rate and Extinction by Water SprinklerCombustion Science and Technology, 1997
- Mechanisms of extinction of liquid fires with water spraysCombustion and Flame, 1960