Method of critical distances for stochastic assessment of voltage sags
Author:
- 1 January 1998
- journal article
- Published by Institution of Engineering and Technology (IET) in IEE Proceedings - Generation, Transmission and Distribution
- Vol. 145 (1) , 70-76
Abstract
A fast method is presented for obtaining a first estimate of the expected number of spurious trips due to voltage sags. The method is based on an expression for the so called critical distance (the radius of the exposed area in which faults lead to equipment trips) in radial systems. Extensions of the method for nonradial systems, and transfer of sags due to single-phase and phase-to-phase faults to lower voltages are also presented.Keywords
This publication has 3 references indexed in Scilit:
- Point of utilization power quality study resultsIEEE Transactions on Industry Applications, 1995
- Predicting and preventing problems associated with remote fault-clearing voltage dipsIEEE Transactions on Industry Applications, 1991
- Diagnosing Power Quality-Related Computer ProblemsIEEE Transactions on Industry Applications, 1979