This paper illustrates the use of a cost function or performance measure to carry out a sensitivity analysis on the Slatt Thyristor Controlled Series Capacitor (TCSC). The sensitivity analysis performed revealed that a choice of controller parameters for optimal system damping are dependent upon the system loading level and configuration. This result suggests that by tuning the control parameters of the TCSC controller for the various system conditions encountered on the power system a significant improvement in system damping may be obtained.Keywords
This publication has 7 references indexed in Scilit:
- Concepts for design of FACTS controllers to damp power swingsIEEE Transactions on Power Systems, 1995
- Bang-bang series capacitor transient stability controlIEEE Transactions on Power Systems, 1995
- Power oscillation damping control strategies for FACTS devices using locally measurable quantitiesIEEE Transactions on Power Systems, 1995
- Synchronized sampling and phasor measurements for relaying and controlIEEE Transactions on Power Delivery, 1994
- Thyristor controlled series compensation prototype installation at the Slatt 500 kV substationIEEE Transactions on Power Delivery, 1993
- Experience with the R-RDOT out-of-Step RelayIEEE Transactions on Power Delivery, 1986
- A New Out-of-Step Relay with Rate of Change of Apparent Resistance AugmentationIEEE Transactions on Power Apparatus and Systems, 1983