Abstract
Incipient faults in underground cables are often resulted from electric stress and cable aging. Appearance of such faults as current spikes in short periods can lead to permanent faults or they may disturb electricity transmissions because of detection delays. Therefore, precise well-timed protection decisions cannot be made. Therefore, one of the most important considerations of utilities in the monitoring process is to recognize these types of faults from other conditions as soon as possible. In this paper, a precise approach based on CU-SUM (CUmulative SUM) and ADAptive Linear NEuron (ADALINE) has been proposed. In addition to its high-speed detection ability, the proposed approach is simple in practical on-line implementation and does not have the complication of other approaches. The simulation results in EMTPWorks environment demonstrate that the proposed approach has a strong capability in distinguishing the cable incipient faults from other similar conditions in distribution systems.