Incipient faults in underground cables are often resulted from electric stress and cable aging. Appearance of such faults as current spikes in short periods can lead to permanent faults or they may disturb electricity transmissions because of detection delays. Therefore, precise well-timed protection decisions cannot be made. Therefore, one of the most important considerations of utilities in the monitoring process is to recognize these types of faults from other conditions as soon as possible. In this paper, a precise approach based on CU-SUM (CUmulative SUM) and ADAptive Linear NEuron (ADALINE) has been proposed. In addition to its high-speed detection ability, the proposed approach is simple in practical on-line implementation and does not have the complication of other approaches. The simulation results in EMTPWorks environment demonstrate that the proposed approach has a strong capability in distinguishing the cable incipient faults from other similar conditions in distribution systems.Keywords
This publication has 25 references indexed in Scilit:
- Incipient fault location method for distribution networks with underground shielded cables: A system identification approachInternational Transactions on Electrical Energy Systems, 2017
- The arcing fault based multi-cycle incipient fault detection for underground cable2016
- Method of cable incipient faults detection and identification based on wavelet transform and gray correlation analysis2016
- Kalman filter based incipient fault detection method for underground cablesIET Generation, Transmission & Distribution, 2015
- Analysis of cable failure modes and cable joint failure detection via sheath circulating current2014
- Security assessment for a cumulative sum-based fault detector in transmission lines2011
- Improved algorithm for detection of self-clearing transient cable faults2008
- Prevention of underground cable splice failuresIEEE Transactions on Industry Applications, 2001
- Manhole explosions due to arcing faults on underground secondary distribution cables in ductsIEEE Transactions on Power Delivery, 1992