Control of Offshore MMC During Asymmetric Offshore AC Faults for Wind Power Transmission
- 22 July 2019
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Journal of Emerging and Selected Topics in Power Electronics
- Vol. 8 (2) , 1074-1083
Abstract
The adoptions of medium-voltage in AC collection networks of large DC connected wind farms significantly increase the AC current magnitudes during normal and fault conditions. Controlling fault currents at zero during asymmetric AC faults is possible, but it has several drawbacks such as increased risk of protection mal-operation due to absence of fault currents, which also tends to prevent the recovery of AC voltage in post-fault. Therefore, this paper presents an enhanced control strategy that exploits the induced negative sequence voltages to facilitate controlled injection of negative sequence currents during asymmetric AC faults. The proposed control not only defines a safe level of fault current in the offshore AC network but also instigates immediate recovery of the AC voltage following clearance of AC faults, which avoid protection mal-operation. In addition, the positive sequence voltage set-point of the offshore modular multilevel converter (MMC) is actively controlled by considering the negative and zero sequence voltages, which effectively avoids the excessive overvoltage in the healthy phases during asymmetrical AC faults. The theoretical basis of the proposed control scheme is described, and its technical viability is assessed using simulations.Keywords
Funding Information
- European Union’s Horizon 2020 Research and Innovation Programme (691714)
This publication has 25 references indexed in Scilit:
- DC Fault Detection and Location in Meshed Multiterminal HVDC Systems Based on DC Reactor Voltage Change RateIEEE Transactions on Power Delivery, 2016
- DolWin1 - Challenges of connecting offshore wind farms2016
- The effect of the offshore VSC-HVDC connected wind power plants on the unbalanced faulted behavior of AC transmission systems2016
- Enhanced Dynamic Voltage Control of Type 4 Wind Turbines During Unbalanced Grid FaultsIEEE Transactions on Energy Conversion, 2015
- Precharging and DC Fault Ride-Through of Hybrid MMC-Based HVDC SystemsIEEE Transactions on Power Delivery, 2014
- A Novel Transient Control Strategy for VSC-HVDC Connecting Offshore Wind Power PlantIEEE Transactions on Sustainable Energy, 2014
- Wind turbine negative sequence current control and its effect on power system protection2013
- Unbalanced-Grid-Fault Ride-Through Control for a Wind Turbine InverterIEEE Transactions on Industry Applications, 2008
- HVDC Connection of Offshore Wind Farms to the Transmission SystemIEEE Transactions on Energy Conversion, 2007
- VSC Transmission Operating Under Unbalanced AC Conditions—Analysis and Control DesignIEEE Transactions on Power Delivery, 2005