The corrosion behaviour of galvanized steel in cooling tower water containing a biocide and a corrosion inhibitor
- 26 February 2013
- journal article
- research article
- Published by Taylor & Francis in Biofouling
- Vol. 29 (3) , 223-235
Abstract
The corrosion behaviour of galvanized steel in cooling tower water containing a biocide and a corrosion inhibitor was investigated over a 10-month period in a hotel. Planktonic and sessile numbers of sulphate reducing bacteria (SRB) and heterotrophic bacteria were monitored. The corrosion rate was determined by the weight loss method. The corrosion products were analyzed by energy dispersive X-ray spectroscopy and X-ray diffraction. A mineralized, heterogeneous biofilm was observed on the coupons. Although a biocide and a corrosion inhibitor were regularly added to the cooling water, the results showed that microorganisms, such as SRB in the mixed species biofilm, caused corrosion of galvanized steel. It was observed that Zn layers on the test coupons were completely depleted after 3 months. The Fe concentrations in the biofilm showed significant correlations with the weight loss and carbohydrate concentration (respectively, p < 0.01 and p < 0.01).Keywords
This publication has 44 references indexed in Scilit:
- Microbially influenced corrosion of galvanized steel pipes in aerobic water systemsJournal of Applied Microbiology, 2010
- Monitoring of Biofilm-associated Legionella pneumophila on Different Substrata in Model Cooling Tower SystemEnvironmental Monitoring and Assessment, 2007
- Investigation of biocide efficacy by photoacoustic biofilm monitoringWater Research, 2004
- Biofilm responses to ageing and to a high phosphate load in a bench-scale drinking water systemWater Research, 2003
- An efficient biofilm removal method for bacterial cells exposed to drinking waterJournal of Microbiological Methods, 1999
- Biofilm formation in a freshwater environment under photic and aphotic conditionsBiofouling, 1997
- Toxicity of heavy metals (Ni, Zn) todesulfovibrio desulfuricansGeomicrobiology Journal, 1997
- Inhibition of the cytochromebd-terminated NADH oxidase system inEscherichia coliK-12 by divalent metal cationsFEMS Microbiology Letters, 1995
- Statistics-based classification of microbially influenced corrosion in freshwater systemsWater Research, 1994
- Microorganisms and heavy metal toxicityMicrobial Ecology, 1977