Analysis of aspects of lightning strokes to large-sized transmission lines
Authors:
- 31 January 2011
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 18 (1) , 182-191
Abstract
When designing large-sized transmission facilities, evaluating the risk of their lightning outage is very important, hence the authors have been conducting a study to determine a more precise method for calculating the lightning stroke rate and the lightning outage rate. In that study, it is essential to clarify the aspect of lightning strokes to large-sized transmission lines. In this context, the Tokyo Electric Power Company has observed lightning strokes to overhead ground wire or transmission tower (shielding success), for the first time as far as the authors are aware, and direct lightning strokes to a phase conductor (shielding failure). The present study analyzed and compared the ratios of shielding success or failure, and the (forward) flashover or back flashover outage rates based on the observation results of UHV-designed and 500 kV transmission lines. The number of lightning strokes to transmission facilities is 167.3 cases/100km/year for UHV-designed transmission lines and 130.8 cases/100km/year for 500 kV transmission lines, meaning the taller the facilities, the more lightning strokes occur. For these lightning strokes, the shielding failure rates were 1.80 and 0.98% for UHV-designed and 500 kV transmission lines, respectively, whereas the lightning outage rates due to direct lightning strokes (flashover) were almost equal at 0.37 and 0.39% for UHV-designed and 500 kV transmission lines, respectively. This is due to the balance between the shielding effect associated with the insulation clearance and the flashover voltage between arcing horns. Conversely, the lightning outage rate due to back flashover was mainly a factor of the distance between arcing horns and was 0.05% for UHV-designed transmission lines, which was very low compared with 0.59% for 500 kV transmission lines. Based on these results, since a comparatively high number of lightning outages were caused by direct lightning strokes on large-sized transmission lines, e.g. UHV class, the need for insulation design to tackle such cases was indicated.Keywords
This publication has 10 references indexed in Scilit:
- Method of calculating the lightning outage rate of large-sized transmission linesIEEE Transactions on Dielectrics and Electrical Insulation, 2010
- Improved method of calculating lightning stroke rate to large-sized transmission lines based on electric geometry modelIEEE Transactions on Dielectrics and Electrical Insulation, 2010
- Observation results of lightning shielding for large-scale transmission linesIEEE Transactions on Dielectrics and Electrical Insulation, 2009
- Observational Results of Lightning Current on Transmission TowersIEEE Transactions on Power Delivery, 2006
- Characteristics of Direct Lightning Strokes to Phase Conductors of UHV Transmission LinesIEEE Transactions on Power Delivery, 2006
- Melting and Breaking Characteristics of OPGW Strands by LightningIEEE Transactions on Power Delivery, 2004
- Modeling of transmission line exposure to direct lightning strokesIEEE Transactions on Power Delivery, 1990
- An Improved Electrogeometric Model for Transmission Line Shielding AnalysisIEEE Transactions on Power Delivery, 1987
- Field and Analytical Studies of Transmission Line Shielding: PartIEEE Transactions on Power Apparatus and Systems, 1969
- Field and Analytical Studies of Transmission Line ShieldingIEEE Transactions on Power Apparatus and Systems, 1968