An alkaline approach to treating cooling towers for control of Legionella pneumophila
Authors:
- 1 August 1987
- journal article
- research article
- Published by American Society for Microbiology in Applied and Environmental Microbiology
- Vol. 53 (8) , 1775-1779
Abstract
Earlier field and laboratory studies have shown that Legionella species survive and multiply in the pH range 5.5 to 9.2. Additionally, the technical feasibility of operating cooling towers at elevated alkalinities and pH has previously been documented by published guidelines. The guidelines indicate that these conditions facilitate corrosion control and favor chlorine persistence which enhances the effectiveness of continuous chlorination in biofouling control. This information suggests that control of Legionella species in cooling towers can be accomplished by operating the towers under alkaline conditions. To test this possibility, we collected water samples over a period of months from a hospital cooling tower. The samples were analyzed for a variety of chemical parameters. Subsamples were pasteurized and inoculated with non-agar-passaged Legionella pneumophila which had been maintained in tap water. Correlation of subsequent Legionella growth with corresponding pH and alkalinity values revealed statistically significant inverse associations. These data support the hypothesis that operating cooling towers outside of the optimal conditions for Legionella growth (e.g., at elevated alkalinities and a pH greater than 9) may be a useful approach to controlling growth in this habitat.Keywords
This publication has 24 references indexed in Scilit:
- Effects of metals on Legionella pneumophila growth in drinking water plumbing systemsApplied and Environmental Microbiology, 1985
- Effectiveness of 1-bromo-3-chloro-5,5-dimethylhydantoin against Legionella pneumophila in a cooling towerApplied and Environmental Microbiology, 1984
- Susceptibility of Legionella pneumophila to chlorine in tap waterApplied and Environmental Microbiology, 1983
- Legionella pneumophila in cooling water systems: Report of a survey of cooling towers in London and a pilot trial of selected biocidesEpidemiology and Infection, 1982
- Susceptibility of Legionella pneumophila to three cooling tower microbicidesApplied and Environmental Microbiology, 1981
- An Outbreak of Legionnaires' Disease Associated with a Contaminated Air-Conditioning Cooling TowerNew England Journal of Medicine, 1980
- Cooling Towers and Evaporative CondensersAnnals of Internal Medicine, 1979
- PONTIAC FEVERAmerican Journal of Epidemiology, 1978
- Factors affecting comparative resistance of naturally occurring and subcultured Pseudomonas aeruginosa to disinfectants.1972