Anti-Interference Measurement Methods of the Coupled Transmission-Line Capacitance Parameters Based on the Harmonic Components
Authors:
- 25 September 2015
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 31 (6) , 2464-2472
Abstract
The traditional measurement methods of capacitance parameters of coupled transmission lines bring large measurement errors under a strong electromagnetic-interference environment. To solve this problem, new anti-interference measurement methods based on harmonic components are proposed. First, the voltages and currents at the head end and the tail end of the transmission line are sampled synchronously based on global positioning system (GPS) technology, then they acquire the third harmonic components from the measured data with an interpolation fast Fourier transform algorithm, and substitute them to the calculation formulae, so that the power frequency interference signals are filtered as noise and the capacitance parameters can be accurately measured. The wiring diagram of line parameter measurement and the hardware structure of the measuring system based on GPS are given. The simulation results with PSCAD and an example of measuring two 200-kV coupled transmission lines are given. The comparison of measurement results between the proposed methods and the traditional methods is also shown.Keywords
Funding Information
- State Key Laboratory of Electrical Insulation and Power Equipment of China
- Specialized Research Fund for Doctoral Program of Higher Education of China (20110141110032)
This publication has 17 references indexed in Scilit:
- Circulating Unbalanced Currents of EHV/UHV Untransposed Double-Circuit Lines and Their Influence on Pilot ProtectionIEEE Transactions on Power Delivery, 2013
- On Powers of Gaussian White NoiseIEEE Transactions on Information Theory, 2011
- A Decision Tree-Based Method for Fault Classification in Double-Circuit Transmission LinesIEEE Transactions on Power Delivery, 2010
- New Method of Live Line Measuring the Inductance Parameters of Transmission Lines Based on GPS TechnologyIEEE Transactions on Power Delivery, 2008
- Bi-directional coupling between two coupled transmission linesIEEE Microwave and Wireless Components Letters, 2003
- A harmonic model for the nonlinearities of single-phase transformer with describing functionsIEEE Transactions on Power Delivery, 2003
- Saturation curves of delta-connected transformers from measurementsIEEE Transactions on Power Delivery, 1995
- Harmonics from SVC transformer saturation with direct current offsetIEEE Transactions on Power Delivery, 1994
- Windows and interpolation algorithms to improve electrical measurement accuracyIEEE Transactions on Instrumentation and Measurement, 1989