Modeling of copper sulphide migration in paper oil insulation of transformers
Authors:
- 2 October 2012
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 19 (5) , 1642-1649
Abstract
Corrosion of copper due to sulphur in oil has affected the performance of transformers. The fundamental processes governing corrosion of copper due to sulphur in oil are still not well understood. In this paper, the dielectric performance of paper oil insulation under conditions of copper sulphide is discussed based on changes in capacitance, Insulation resistance and Partial discharges. Electric field analysis using FEM and PD results are employed to develop an empirical model to predict PD inception of paper oil insulation when copper sulphide is present. A simple model is also proposed to explain progressive copper sulphide migration in paper insulation. The non-linear V-I characteristics of copper sulphide is discussed to explain the breakdown of paper-oil insulation.Keywords
This publication has 6 references indexed in Scilit:
- Dielectric Loss Characteristics of Copper-Contaminated Transformer OilsIEEE Transactions on Power Delivery, 2010
- Corrosive sulfur effects in transformer oils and remedial proceduresIEEE Transactions on Dielectrics and Electrical Insulation, 2009
- Corrosive Sulfur Induced Failures in Oil-Filled Electrical Power Transformers and Shunt ReactorsIEEE Transactions on Power Delivery, 2009
- Highly sensitive detection method of dibenzyl disulfide and the elucidation of the mechanismIEEE Transactions on Dielectrics and Electrical Insulation, 2009
- Duration and mechanism for suppressive effect of triazole-based passivators on copper-sulfide deposition on insulating paperIEEE Transactions on Dielectrics and Electrical Insulation, 2009
- Identification of affecting factors of copper sulfide deposition on insulating paper in oilIEEE Transactions on Dielectrics and Electrical Insulation, 2009