Scheme for synchronous machine stator turn‐to‐turn protection
Open Access
- 3 February 2020
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in IET Electric Power Applications
- Vol. 14 (4) , 716-722
Abstract
This study presents a new protection scheme for turn‐to‐turn fault protection in the stator windings of synchronous machines. The main difference with other methods is the calculation of voltage of the winding from the phase to ground and neutral to ground voltages, which can be obtained from the monitoring provided by any commercial generator multifunction protection relay. This new method allows the employment of the protection transformers already installed in the protection scheme, simplifying and reducing the cost of the protection function. To validate this new technique, finite element method simulations and numerous tests have been performed in a specially built synchronous generator with taps in one of the stator windings. In this way, several turn‐to‐turn faults have been created at different fault severity levels.Keywords
This publication has 22 references indexed in Scilit:
- Modified magnetic‐equivalent‐circuit approach for various faults studying in saturable double‐cage‐induction machinesIET Electric Power Applications, 2017
- Detection of Inter-Turn Stator Faults in Induction Motors Using Short-Term Averaging of Forward and Backward Rotating Stator Current Phasors for Fast PrognosticsIEEE Transactions on Magnetics, 2017
- Efficient method for discrimination between inrush current and internal faults in power transformers based on the non‐saturation zoneIET Generation, Transmission & Distribution, 2017
- Stator winding inter‐turn short‐circuit detection in induction motors by parameter identificationIET Electric Power Applications, 2017
- An Inverse Approach for Interturn Fault Detection in Asynchronous Machines Using Magnetic Pendulous Oscillation TechniqueIEEE Transactions on Industry Applications, 2015
- On-line stator ground-fault location method for synchronous generators based on 100% stator low-frequency injection protectionElectric Power Systems Research, 2015
- Mitigation of Turn-to-Turn Faults in Fault Tolerant Permanent Magnet Synchronous MotorsIEEE Transactions on Energy Conversion, 2014
- Transient Analysis of Irreversible Demagnetization of Permanent-Magnet Brushless DC Motor With Interturn Fault Under the Operating StateIEEE Transactions on Industry Applications, 2014
- Condition monitoring and diagnostics of motor and stator windings – A reviewIEEE Transactions on Dielectrics and Electrical Insulation, 2013
- Stator Interturn Fault Detection of Synchronous Machines Using Field Current and Rotor Search-Coil Voltage Signature AnalysisIEEE Transactions on Industry Applications, 2009