Converter side phase-to-ground fault protection of full-bridge modular multilevel converter-based bipolar HVDC

Authors:

Abstract
This study proposed a novel protective action for converter side phase-to-ground fault of FB-MMC-based bipolar HVDC. The faulty converter is kept in operation during fault, and its dc-link voltage reference is set to zero in order to avoid serious overvoltage of the sub-module capacitors. This protective action was verified by simulation. The overcurrent and overvoltage of converter arms are moderate when adopting this protective action.