Carbon dioxide generation calorimetry—Errors induced by the simplifying assumptions in the standard test methods
Authors:
Open Access
- 9 January 2009
- journal article
- research article
- Published by Wiley in Fire and Materials
- Vol. 33 (2) , 89-97
Abstract
Carbon dioxide generation (CDG) calorimetry is commonly used for measuring heat release rates of materials. Calorimetric equation provided in the ASTM E 2058 and the NFPA code 287 is a simplified equation since the water content in the ambient air and the fumes as well as the expansion factor of the combustion gases are neglected. This paper provides general equation for CDG calorimetry based on the Tewarson formulation. A comparison is proposed between the Standard test methods (simplified equation) and the general one. It is shown that the errors induced by the simplifying assumptions are negligible for oxygen depletion factor values commonly encountered in the Fire Propagation Apparatus (where large dilution factors of the combustion gases are used before the measurements of species concentrations). Copyright © 2009 John Wiley & Sons, Ltd.Keywords
This publication has 4 references indexed in Scilit:
- Uncertainty analysis of heat release rate measurement from oxygen consumption calorimetryFire and Materials, 2005
- Uncertainty of Heat Release Rate Calculation of the ISO5660–1 Cone Calorimeter Standard Test MethodFire Technology, 1999
- Measuring rate of heat release by oxygen consumptionFire Technology, 1991
- Calculations of the Heat Release Rate by Oxygen Consumption for Various ApplicationsJournal of Fire Sciences, 1984