Insulation characteristics of 1100 kV GIS under very fast transient overvoltage and lightning impulse
Authors:
- 15 June 2012
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 19 (3) , 1029-1036
Abstract
Very fast transient overvoltage (VFTO) in gas insulated switchgear (GIS) is of great concern at the higher rated voltages because the difference between the rated lightning impulse (LI) and the VFTO withstand voltage decreases. In order to clarify VFTO withstand level of 1100 kV GIS, a simulation system was designed for generation of VFTO. The breakdown characteristics of sphere-plane gap and rod-plane gap in SF6 under VFTO and LI were investigated for different gas pressures. Experimental results show that the breakdown voltages in slightly inhomogeneous field gaps under VFTO are higher than that under LI. However, for the rod-plane gaps, the breakdown voltages and voltage-time curves under VFTO fall below that of LI at higher pressure in the case of negative polarity. The polarity effect of rod-plane gaps under LI is reversed at a certain pressure. Based on the analyses, it is concluded that the different breakdown characteristics of SF6 gaps may be attribute to the difference between space charge behaviors during the discharge development under the impulse with different wave front and oscillation tail of VFTO and LI.Keywords
This publication has 29 references indexed in Scilit:
- Evaluation of breakdown characteristics of gas insulated switchgears for non-standard lightning impulse waveforms - breakdown characteristics under non-uniform electric fieldIEEE Transactions on Dielectrics and Electrical Insulation, 2008
- Partial discharges and breakdown at protrusions in uniform background fields in SF6Journal of Physics D: Applied Physics, 2008
- Measured Lifetime ofPhysical Review Letters, 2008
- Effect of initiatory electrons on breakdowncharacteristics of SF 6 and its mixturesIEE Proceedings - Science, Measurement and Technology, 2001
- A study of alternative insulating gases to SF6Journal of Physics D: Applied Physics, 1999
- Transient Impulse Breakdowns of SF6Gas in Inhomogeneous Electric FieldsJapanese Journal of Applied Physics, 1999
- The pressure dependence of the leader stepping time for a positive point-plane gap in gasJournal of Physics D: Applied Physics, 1998
- Prediction of breakdown in SF/sub 6/ under impulse conditionsIEEE Transactions on Dielectrics and Electrical Insulation, 1996
- A Review of Particle-Contaminated Gas BreakdownIEEE Transactions on Electrical Insulation, 1981
- Variation of Breakdown Voltage of a Positive-point/Plane Gap with Applied Voltage WaveshapeNature, 1965