Bond performance of grouted tendons at elevated temperatures

Authors:

Abstract
The bond between tendons and grout is crucial to the performance of bonded post-tensioned concrete structures. To study the bond performance of grouted tendons at elevated temperatures, pull-out tests were conducted on specimens comprising either a mono- or multi-strand tendon located centrally within a grouted duct inside a concrete cylinder, at test temperatures of 20–600°C. It was found that the bond strength deteriorated with a rise in temperature and the degradation of bond strength was more severe than that of other mechanical properties. Three types of failure mode were observed: pull-out, partial splitting and through splitting. The use of a smaller duct could improve the bond strength of specimens failing in pull-out mode. The influence of the strength of the outer concrete was found to be insignificant. Based on the distinct bond behaviour of different failure modes, a bond–slip model was developed by regression of the test results.