Ground Fault Overvoltage With Inverter-Interfaced Distributed Energy Resources
Authors:
Open Access
- 7 June 2016
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 32 (2) , 890-899
Abstract
Ground fault overvoltage can occur in situations in which a four-wire distribution circuit is energized by an ungrounded voltage source during a single-phase-to-ground fault. The phenomenon is well documented with ungrounded synchronous machines, but there is considerable discussion about whether inverters cause this phenomenon and, consequently, whether inverters require effective grounding. This paper examines the overvoltages that can be supported by inverters during single-phase-to ground faults via theory, simulation, and experiment. It identifies the relevant physical mechanisms, quantifies expected levels of overvoltage, and makes recommendations for optimal mitigation. It concludes that under many circumstances, effective grounding of inverters is not necessary to prevent ground fault overvoltage.Keywords
Funding Information
- U.S. Department of Energy (DE-AC36-08GO28308)
- National Laboratory of the Rockies
- SolarCity Corporation (CRD-14-563)
This publication has 5 references indexed in Scilit:
- Inverter Ground Fault Overvoltage Testing2015
- Sequence impedance measurement of three-phase inverters using a parallel structure2015
- Temporary Overvoltage and GPR Characteristics of Distribution Feeders With Multigrounded NeutralIEEE Transactions on Power Delivery, 2009
- Overvoltage considerations in applying distributed resources on power systems2003
- Overvoltage Considerations for Interconnecting Dispersed Generators with Wye-Grounded Distribution FeedersIEEE Transactions on Power Apparatus and Systems, 1984