Enclosed liquid natural convection as a means of transferring heat from microelectronics to cold plates
Authors:
- 1 March 2013
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- No. 10652221,p. 60-64
Abstract
Liquid immersion of datacom electronics can be configured as a cooling mechanism when components are in direct contact with a high dielectric strength liquid. This paper analyses the heat transfer capabilities of datacom electronics when they are enclosed in a cassette with a dielectric liquid and sandwiched against a cold plate positioned in parallel with the printed circuit board. A proxy server motherboard with controllable heat cells and temperature sensors is used to conduct a series of heat transfer experiments. The results of which demonstrate that the thermal conductance processes via the naturally convecting dielectric liquid improves as the power demand of the electronics increases.Keywords
This publication has 7 references indexed in Scilit:
- Computational fluid dynamic investigation of liquid rack cooling in data centresApplied Energy, 2012
- The merits of open bath immersion cooling of datacom equipment2010
- Fin Pattern Effects on Air-Side Heat Transfer and Friction Characteristics of Fin-and-Tube Heat Exchangers with Large Number of Large-Diameter Tube RowsHeat Transfer Engineering, 2009
- The evolution of water cooling for IBM large server systems: Back to the future2008
- Direct Liquid Cooling of High Flux Micro and Nano Electronic ComponentsProceedings of the IEEE, 2006
- Maintaining Datacom Rack Inlet Air Temperatures With Water Cooled Heat Exchanger2005
- High-performance heat sinking for VLSIIEEE Electron Device Letters, 1981