Output LC filter design of voltage source inverter considering the performance of controller
Authors:
- J. ChoiJCJ. Choi
- H. HongHHH. Hong
- 11 November 2002
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- Vol. 3, 1659-1664
Abstract
The LC filter design procedure of the inverter output filter is described. The transfer function of the filter output voltage to the load current is described with the capacitor value and the system time constant considering the system controller. By using the closed form of the relation between the filter capacitor value and the system time constant, the capacitor value can be calculated with the given system time constant and vice versa. It is more practical for the implementation of power and control circuit of inverter. And, as the effect of the load current to the voltage distortion can be calculated from the closed form, it is possible to analyze the system in how much the voltage waveform is distorted in case of the nonlinear load. All the proposed design procedure is verified with the simulation and experimental results.Keywords
This publication has 5 references indexed in Scilit:
- Importance of coefficient diagram in polynomial method2004
- Output impedance of PWM UPS inverter-feedback vs. filters2002
- Towards a zero-output impedance UPS systemIEEE Transactions on Industry Applications, 1989
- Optimum Input and Output Filters for a Single-Phase Rectifier Power SupplyIEEE Transactions on Industry Applications, 1981
- Optimum Filter Design for a Single-Phase Solid-State UPS SystemIEEE Transactions on Industry Applications, 1979